Hitachi ABB Power Grids has updates available to handle an improper input validation vulnerability in its Relion 670, 650, and SAM600-IO; REB500; RTU500; FOX615 (TEGO1); MSM; GMS600, and PWC600, according to a report with CISA.

Successful exploitation of this remotely exploitable vulnerability, discovered by Markus Mahrla, GAI NetConsult GmbH and Lars Lengersdorf, Amprion GmbH, could reboot the device regularly, resulting in a denial-of-service condition. During the reboot phase, the primary functionality of the device is not available.

Products affected by the issue include:

  • Relion 670 series Version 1.1, all revisions
  • Relion 670 series Version 1.2.3, all revisions
  • Relion 670 series Version 2.0, all revisions
  • Relion 670/650 series Version 2.1, all revisions
  • Relion 670/650 series Version 2.2.0, all revisions
  • Relion 670/650/SAM600-IO series Version 2.2.1, all revisions
  • Relion 670 series Version 2.2.2, all revisions
  • Relion 670 series Version 2.2.3, all revisions
  • Relion 650 series Version 1.1, all revisions
  • Relion 650 series Version 1.2, all revisions
  • Relion 650 series Version 1.3, all revisions
  • RTU500 CMU firmware release 7.x
  • RTU500 CMU firmware release 8.x
  • RTU500 CMU firmware release 9.x
  • RTU500 CMU firmware release 10.x
  • RTU500 CMU firmware release 11.x
  • RTU500 CMU firmware release 12.x
  • REB500 7.3
  • REB500 7.4
  • REB500 7.5
  • REB500 7.6
  • REB500 8.2
  • REB500 8.3
  • TEGO1 service unit of FOX615 with ESW Version R1D02 and prior
  • MSM: All versions before 2.1.0
  • GMS600 Versions 1.3.0 and prior
  • PWC600 Version 1.0
  • PWC600 Version 1.1

In the vulnerability, an attacker with access to the IEC 61850 network with knowledge of how to reproduce the attack, as well as the IP addresses of the different IEC 61850 access points (of IEDs/products), can force the device to reboot, which renders the device inoperable for approximately 60 seconds. This vulnerability affects only products with IEC 61850 interfaces.

CVE-2021-27196 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 7.5.

Schneider Bold

The product sees use mainly in the energy sector, and it sees action on a global basis.

No known public exploits specifically target this vulnerability. However, an attacker with low skill level could leverage the vulnerability.

Hitachi ABB Power Grids recommends users apply relevant updates at their earliest convenience. Contact Hitachi ABB Power Grids to acquire firmware on a specific product version. Hitachi ABB Power Grids created these new versions to address the vulnerability:

  • PWC600 Version 1.0.1.4
  • PWC600 Version 1.1.0.1
  • GMS600 Version 1.3.1
  • MSM Version 2.1.0+ (All older versions might be affected)
  • FOX615 TEGO1 Version R2A16 and later
  • REB500 7.6 Version 7.60.19
  • REB500 8.2 Version 8.2.0.5
  • REB500 8.3 Version 8.3.1.0
  • For REB500 7.3, 7.4, and 7.5, it is recommended to migrate to the REB500 7.6 Version 7.60.19 or later
  • RTU500 CMU firmware release 12.6.1.0
  • RTU500 CMU firmware release 12.4.10.0 (planned)
  • RTU500 CMU firmware release 12.2.11.0 (planned)
  • RTU500 CMU firmware release 12.0.14.0 (planned)
  • For RTU500 series version of release 11 and older, migration to latest release 12 is recommended
  • Relion 670 series Version 1.1: Please follow recommendation as listed in the mitigation factor section or upgrade to the latest product version. For upgrades, please contact Hitachi ABB Power Grids.
  • Relion 670 series Version 1.2.3: Fixed in revision 670 1.2.3.20
  • Relion 670 series Version 2.0: Planned
  • Relion 670 series Version 2.1: Planned
  • Relion 670/650 series Version 2.2.0: Fixed in revision 670 2.2.0.13
  • Relion 670/650/SAM600-IO series Version 2.2.1: Fixed in revision 670 2.2.1.6
  • Relion 670 series Version 2.2.2: Fixed in revision 670 2.2.2.3
  • Relion 670 series Version 2.2.3: Fixed in revision 670 2.2.3.2
  • Relion 650 series Version 1.1: Planned
  • Relion 650 series Version 1.2: Please follow recommendation as listed in the mitigation factor section or upgrade to product Version 1.3. For upgrades, please contact Hitachi ABB Power Grids.
  • Relion 650 series Version 1.3: Fixed in revision 650 1.3.0.7

Not connecting the affected products to any station network through the LAN port (optical or RJ45) should make above attack physically impossible. The functionality of the system would have to be maintained by giving switching commands through hardwired binary inputs. This vulnerability affects only products with IEC 61850 interfaces.

Please see the Hitachi ABB Power Grids advisory for this issue in each of the products:

Recommended security practices and firewall configurations can help protect a process control network from attacks originating from outside the network. Such practices include process control systems physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and are separated from other networks by means of a firewall system with a minimal number of ports exposed. Other systems would be evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or receiving emails. Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system.

More information on recommended practices can be found in the cybersecurity deployment guidelines for each product version.

Pin It on Pinterest