Inductive Automation has an upgrade and workaround available to handle an improper access control vulnerability in its Ignition 8 Gateway, according to a report with CISA.
Successful exploitation of this remotely exploitable vulnerability, discovered by Sharon Brizinov and Mashav Sapir from Claroty, could allow an attacker to write endless log statements into the database, which could result in a denial-of-service condition.
The following versions of Ignition 8 Gateway end up affected if running the Perspective Module: Versions prior to 8.0.10.
In the vulnerability, there is an unprotected logging route that may allow an attacker to write endless log statements into the database without space limits or authentication. This could result in consuming the entire available hard-disk space, causing a denial-of-service condition.
CVE-2020-10641 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 9.1.
The product sees use in the critical manufacturing, energy, and information technology sectors. It also sees action mainly in the United States.
No known public exploits specifically target this vulnerability. However, an attacker with low skill level could leverage the vulnerability.
Inductive Automation recommends the following mitigation: Upgrade to Ignition 8 Gateway to v8.0.10.
The following workarounds are suggested if users cannot upgrade to v8.0.10 or above:
- If running the Perspective Module, set “perspective.routes” to a priority level of WARN or higher. The exploit triggers the code path that logs a message with priority level INFO.
- For gateways deployed behind a web application firewall or reverse proxy, deploy a rule to deny access to all gateway HTTP requests that include the path: /data/perspective/print-to-log.