Inductive Automation has an update for its upgrade that is available to handle missing authentication for critical function, and deserialization of untrusted data vulnerabilities in its Ignition, according to a report with CISA.
Successful exploitation of these remotely exploitable vulnerabilities, discovered by Pedro Ribeiro, Radek Domanski, Chris Anastasio (muffin), and Steven Seeley (mr_me) working with Trend Micro’s Zero Day Initiative, could allow an attacker to obtain sensitive information and perform remote code execution with system privileges.
The following versions suffer from the issues:
- Inductive Automation Ignition 7 Gateway versions prior to 7.9.14
- Inductive Automation Ignition 8 Gateway versions prior to 8.0.10
In one issue, the affected product lacks proper authentication required to query the server.
CVE-2020-12004 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 5.3.
In addition, the affected product lacks proper validation of user-supplied data, which can result in deserialization of untrusted data.
CVE-2020-10644 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 9.8.
Also, the affected product is vulnerable to the handling of serialized data. The issue results from the lack of proper validation of user-supplied data, which can result in deserialization of untrusted data.
CVE-2020-12000 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 9.8.
In addition, sensitive information can end up obtained through the handling of serialized data. The issue results from the lack of proper authentication required to query the server.
CVE-2020-14479 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 5.3.
The product sees use mainly in the critical manufacturing, energy, and information technology sectors. It also sees action in the United States.
No known public exploits specifically target these vulnerabilities. However, an attacker with low skill level could leverage the vulnerabilities.
For those running v7.9.x, it is recommended to upgrade the Ignition software to v7.9.14
As for version 8, Inductive Automation recommends upgrading to Ignition software to v8.0.10.
At present, CVE-2020-14479 does not have a fix in place. Induction Automation plans to correct this vulnerability in future product versions.
It is recommended to restrict interaction with the service to trusted machines. Only clients and servers with a legitimate procedural relationship should be permitted to communicate with the service. This can be done in various ways, most notably with firewall rules/allow listing. For more information regarding software and patches, click on the specified version in Inductive Automation’s release notes.