Rockwell Automation has new versions to handle multiple vulnerabilities in its FactoryTalk View SE, according to a report with CISA.

The remotely exploitable vulnerabilities are an improper input validation, improper restriction of operations within the bounds of a memory buffer, permissions, privileges, and access controls, and exposure of sensitive information to an unauthorized actor.

Successful exploitation of these vulnerabilities, which Rockwell discovered working with Trend Micro’s Zero Day Initiative, may allow a remote authenticated attacker to manipulate data of affected devices. All versions of FactoryTalk View SE are affected.

In one of the issues, the affected product does not properly validate input of filenames within a project directory. A remote, unauthenticated attacker may be able to execute a crafted file on a remote endpoint that may result in remote code execution (RCE).

Schneider Bold

CVE-2020-12029 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 9.0.

In addition, after bypassing memory corruption mechanisms found in the operating system, a local, authenticated attacker may corrupt the associated memory space allowing for arbitrary code execution.

CVE-2020-12031 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 7.5.

Also a remote, authenticated attacker may be able to utilize certain handlers to interact with the data on the remote endpoint since those handlers do not enforce appropriate permissions.

CVE-2020-12028 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 7.3.

In another vulnerability, the affected product discloses the hostnames and file paths for certain files within the system. A remote, authenticated attacker may be able to leverage this information for reconnaissance efforts.

CVE-2020-12027 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 4.3.

The product sees use in the chemical, commercial facilities, critical manufacturing, energy, government facilities, and water and wastewater systems sectors. It also sees action on a global basis.

No known public exploits specifically target these vulnerabilities. However, an attacker with low skill level could leverage the vulnerabilities.

Rockwell released new versions of the affected products to mitigate the reported vulnerabilities. Affected users who are not able to apply the latest update are encouraged to seek additional mitigations or workarounds from the vendor’s published guidelines in their security advisory.

For CVE-2020-12029 Rockwell Automation recommends applying patch 1126289. Before installing this patch, the patch rollup dated April 6 or later must be applied. 1066644 – Patch Roll-up for CPR9 SRx.

For CVE-2020-12031 Rockwell Automation recommends applying patch 1126290. Before installing this patch, the patch rollup dated April 6 or later must be applied. 1066644 – Patch Roll-up for CPR9 SRx.

For CVE-2020-12028 and CVE-2020-12027 Rockwell Automation recommends enabling built in security features found within FactoryTalk View SE. Users should follow guidance found in knowledge base articles 109056 and 1126943 to set up IPSec and/or HTTPs.