Rockwell Automation has a series of fixes available for multiple vulnerabilities in its MicroLogix 1400 Controllers, MicroLogix 1100 Controllers, and RSLogix 500 Software, according to a report with CISA.

The vulnerabilities include a use of hard-coded cryptographic key, use of a broken or risky algorithm for password protection, use of client-side authentication, and cleartext storage of sensitive information.

Successful exploitation of these remotely exploitable vulnerabilities could allow an attacker to gain access to sensitive project file information including passwords. Ilya Karpov, Evgeny Druzhinin from independent research team ScadaX Security and Dmitry Sklyarov from Positive Technologies, as well as Rongkuan Ma, Xin Che, and Peng Cheng from 307 Lab, reported these vulnerabilities to Rockwell.

The following versions of Rockwell Automation products are affected:

Schneider Bold
  • MicroLogix 1400 Controllers
  • Series B v21.001 and prior
    Series A, all versions

  • MicroLogix 1100 Controller, all versions
  • RSLogix 500 Software v12.001 and prior
  • In one issue, the cryptographic key utilized to help protect the account password is hard coded into the RSLogix 500 binary file. An attacker could identify cryptographic keys and use it for further cryptographic attacks that could ultimately lead to a remote attacker gaining unauthorized access to the controller.

    CVE-2020-6990 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 9.8.

    In addition, the cryptographic function utilized to protect the password in MicroLogix is discoverable.

    CVE-2020-6984 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 9.8.

    Also, a remote, unauthenticated attacker can send a request from the RSLogix 500 software to the victim’s MicroLogix controller. The controller will then respond to the client with used password values to authenticate the user on the client-side. This method of authentication may allow an attacker to bypass authentication altogether, disclose sensitive information, or leak credentials.

    CVE-2020-6988 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 7.5.

    In another issue, if Simple Mail Transfer Protocol (SMTP) account data is saved in RSLogix 500, a local attacker with access to a victim’s project may be able to gather SMTP server authentication data as it is written to the project file in cleartext.

    CVE-2020-6980 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 4.0.

    The product sees use in multiple industry sectors, and it sees action on a global basis.

    No known public exploits specifically target these vulnerabilities. However, an attacker with low skill level could leverage the vulnerabilities.

    For MicroLogix 1400 series B controllers, Rockwell recommends affected users apply FRN 21.002 or later for MicroLogix 1400 Series B devices and use the enhanced password security feature.

    Rockwell reports there are currently no mitigations for MicroLogix 1400 series A controllers or MicroLogix 1100 controllers.

    For RSLogix 500 software, Rockwell Automation recommends affected users apply v11 or later and use in conjunction with applied FRN 21.001 or later for Micrologix 1400 Series B devices. Other configurations do not have direct mitigations.

    Pin It on Pinterest

    Share This