Rockwell Automation has a patch and mitigation to handle improper restriction of operations within the bounds of a memory buffer and SQL injection vulnerabilities in its EDS Subsystem, according to a report with CISA.
Successful exploitation of these vulnerabilities, which are exploitable from an adjacent network, could lead to a denial-of-service condition. Sharon Brizinov and Amir Preminger (VP Research) of Claroty discovered these vulnerabilities.
The following products using the EDS Subsystem (Version 28.0.1 and prior) suffer from the issues:
- FactoryTalk Linx software (Previously called RSLinx Enterprise): Versions 6.00, 6.10, and 6.11
- RSLinx Classic: Version 4.11.00 and prior
- RSNetWorx software: Version 28.00.00 and prior
- Studio 5000 Logix Designer software: Version 32 and prior
In one issue, a memory corruption vulnerability exists in the algorithm that matches square brackets in the EDS subsystem. This may allow an attacker to craft specialized EDS files to crash the EDSParser COM object, leading to denial-of-service conditions.
CVE-2020-12038 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 6.7.
In addition, the EDS subsystem does not provide adequate input sanitization, which may allow an attacker to craft specialized EDS files to inject SQL queries and manipulate the database storing the EDS files. This can lead to denial-of-service conditions.
CVE-2020-12034 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 8.2.
The product sees use mainly in the critical manufacturing, energy, and water and wastewater systems sectors. It also sees action on a global basis.
No known public exploits specifically target these vulnerabilities. However, an attacker with low skill level could leverage the vulnerabilities.
Rockwell Automation recommends the following:
- Apply patch by following the instructions in Knowledgebase Article RAid 1125928 (login required).
- Block all traffic to EtherNet/IP or other CIP protocol-based devices from outside the manufacturing zone by blocking or restricting access to TCP Ports 2222, 7153 and UDP Port 44818 using proper network infrastructure controls, such as firewalls, UTM devices, or other security appliances. For more information on TCP/UDP ports used by Rockwell Automation products, see Knowledgebase Article ID 898270
- Locate control system networks and devices behind firewalls and isolate them from the business network.
- When remote access is required, use secure methods, such as virtual private networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
Network-based vulnerability mitigations for embedded products:
General mitigations:
For more information please refer to Rockwell Automation’s security advisory 54102-Industrial Security Advisory Index.