Schneider Electric has a fix available to handle an improper privilege management vulnerability in its EcoStruxure Operator Terminal Expert, according to a report with CISA.

Successful exploitation of this vulnerability, discovered by Lasse Trolle Borup of the Danish Cyber Defence, may allow unauthorized command execution by a local user of the Windows engineering workstation, which could result in loss of availability, confidentiality, and integrity of the workstation running EcoStruxure Operator Terminal Expert runtime.

Schneider Electric reports the vulnerability affects the following EcoStruxure Operator Terminal Expert products:

  • EcoStruxure Operator Terminal Expert Runtime 3.1 Service Pack 1A and prior installed on:
  • Windows PC using legacy BIOS
  • Harmony iPC (HMIG5U, HMIG5U2) using legacy BIOS

Windows PCs using UEFI do not suffer from this vulnerability.

Schneider Bold

In the issues, an improper privilege management vulnerability exists that could cause privilege escalation on the workstation when interacting directly with a driver installed by the runtime software of EcoStruxure Operator Terminal Expert.

CVE-2020-7544 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 7.4.

The product sees use in the commercial facilities, energy, food and agriculture, government facilities, transportation systems, and water and wastewater systems sectors. It also sees action on a global basis.

No known public exploits specifically target this vulnerability. This vulnerability is not exploitable remotely. High skill level is needed to exploit.

Schneider Electric prepared Version 3.1 Service Pack 1B of the EcoStruxure Operator Terminal Expert product with a fix for this vulnerability. This fix is also available through Schneider Electric Software Update (SESU).

If users choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:

  • Use EcoStruxure Operator Terminal Expert runtime software only on a trusted workstation.
  • Harden workstation following the best cybersecurity practices (antivirus, updated operating systems, strong password policies, application white listing software, etc.) by following Schneider Electric’s best practices guidelines. https://www.se.com/us/en/download/document/CS-Best-Practices-2019-340/
  • Use Windows PC with UEFI technology. Users can identify if their PC uses the UEFI technology by using the following system command: msinfo32.exe provided by Microsoft Windows. This command provides the system information. The section BIOS mode displays either “UEFI” or “LEGACY”. (If the value is UEFI, the PC is not vulnerable, if the value is LEGACY then the PC is vulnerable.)

For further information refer to SEVD-2020-315-02.