Schneider Electric has a new version that handles an improper check for unusual or exceptional conditions vulnerability in its PLC Simulator for EcoStruxure Control Expert, according to a report with CISA.
Successful exploitation of this remotely exploitable vulnerability, discovered by Parity Dynamics Research Team, could cause a denial-of-service condition, which could result in a failure of the EcoStruxture Control Expert Simulator.
The vulnerability affects the following PLC simulators:
- PLC Simulator for EcoStruxure Control Expert, all versions
- PLC Simulator for Unity Pro (former name of EcoStruxure Control Expert), all versions
In the issue, a vulnerability exists that could cause a crash of the PLC simulator present in EcoStruxure Control Expert software when receiving a specially crafted request over Modbus.
CVE-2020-7538 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 7.5.
The product sees use in the commercial facilities, energy, food and agriculture, government facilities, transportation systems, and water and wastewater systems sectors. It also sees action on a global basis.
No known public exploits specifically target this vulnerability. However, an attacker with low skill level could leverage the vulnerability.
Schneider Electric released Version 15.0 of the EcoStruxure Control Expert software to mitigate this vulnerability. It is available for download on the Schneider Electric website.
After downloading the fix, users must follow this step to mitigate the vulnerability: In the option dialog box of the PLC simulator, set the listening IP Address to 127.0.0.1 (localhost), which will prevent remote network connections to the PLC simulator.
The default listening IP address is: 0.0.0.0. The default setting exposes the PLC to the vulnerability described in this advisory.
Schneider Electric recommends using appropriate patching methodologies when applying these patches. It also recommends the use of back-ups and evaluating the impact of these patches in a test and development environment or on offline infrastructure. Contact Schneider Electric’s Customer Care Center for assistance removing a patch.
If users choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:
- Set up network segmentation and implement a firewall to block all unauthorized access to Port 502/TCP
- Harden the engineering workstation running PLC Simulator for EcoStruxure Control Expert
- Follow workstation, network, and site-hardening guidelines in the Cybersecurity Best Practices guide.
Click on Schneider Electric Security Notification number SEVD-2020-315-01 for more information.