Schneider Electric has mitigations available to handle an exposure of sensitive information to an unauthorized actor vulnerability in its Modicon X80, according to a report with CISA.

Successful exploitation of this remotely exploitable vulnerability, discovered by Chizuru Toyama of TXOne IoT/ICS Security Research Labs of Trend Micro, may result in information disclosure to an unauthenticated remote user, which could result in an understanding of the network architecture.

The following versions of Modicon X80 suffer from the issue: Modicon X80 BMXNOR0200H RTU SV1.70 IR22 and prior.

In the exposure of sensitive information to an unauthorized actor vulnerability, it could cause an information leak concerning the current RTU configuration including communication parameters dedicated to telemetry when a specially crafted HTTP request is sent to the web server of the module.

CVE-2021-22749 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 5.3.

Schneider Bold

The product sees use in the commercial facilities, critical manufacturing, and energy sectors. It also sees action on a global basis.

No known public exploits specifically target this vulnerability. However, an attacker with low skill level could leverage the low complexity vulnerability.

Schneider recommends users immediately apply the following mitigations to reduce the risk of exploitation until a remediation plan is available:

  • Web access service is disabled by default. Because the web server is only necessary for specific maintenance and configuration activities, it is advised users disable the web (HTTP) service when it is not needed through the Ecostruxure Control Expert application.
  • Set up network segmentation and implement a firewall to block all unauthorized access to HTTP Port 80/TCP on the controllers.
  • When used in an architecture including a BMXNOC module, configure the Access Control Lists following the recommendation in the Modicon Controllers Platform Cyber Security Reference Manual. 

Additional recommended best practice: Change the default password used to access the device web server. Update username and password for HTTP access rights with the “Security” link on the Setup page. See the Modicon X80 BMXNOR0200H RTU Module User Manual. 

Click on Schneider Electric’s publication SEVD-2021-159-05 for more information. 