Siemens has upgrades available to handle unquoted search path or element, uncontrolled resource consumption, and an improper input validation vulnerabilities in its UMC Stack, according to a report with CISA.

Successful exploitation of these remotely exploitable vulnerabilities, discovered by Victor Fidalgo of INCIBE and Reid Wightman of Dragos, could allow an attacker to cause a partial denial-of-service condition on the UMC component of the affected devices under certain circumstances. This could also allow an attacker to locally escalate privileges from a user with administrative privileges to execute code with SYSTEM level privileges.

Siemens said some of the vulnerabilities affect the following UMC components:

  • Opcenter Execution Discrete: All versions prior to v3.2
  • Opcenter Execution Foundation: All versions prior to v3.2
  • Opcenter Execution Process: All versions prior to v3.2
  • Opcenter Intelligence: All versions
  • Opcenter Quality: All versions prior to v11.3
  • Opcenter RD&L: v8.0
  • SIMATIC IT LMS: All versions
  • SIMATIC IT Production Suite: All versions
  • SIMATIC Notifier Server for Windows: All versions
  • SIMATIC PCS neo: All versions
  • SIMATIC STEP 7 (TIA Portal) v15: All versions
  • SIMATIC STEP 7 (TIA Portal) v16: All versions prior to V16 Update 2
  • SIMOCODE ES: All versions
  • Soft Starter ES: All versions

For a complete list of which specific vulnerabilities affect each of these products, click on Siemens security advisory SSA-841348.

Schneider Bold

In one vulnerability, a component within the affected application calls a helper binary with SYSTEM privileges during startup while the call path is not quoted.

CVE-2020-7581 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 6.7.

In addition, sending multiple specially crafted packets to the affected service could cause a partially remote denial of service, which would cause the service to restart itself.

CVE-2020-7587 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 6.5.

Also, sending a specially crafted packet to the affected service could cause a partially remote denial of service, which would cause the service to restart itself.

CVE-2020-7588 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 5.3.

The product sees action mainly in the critical manufacturing sector, and on a global basis.

No known public exploits specifically target these vulnerabilities. However, an attacker with low skill level could leverage the vulnerabilities.

Siemens recommends users upgrade affected products if upgrade are available for those products:

For products that do not have an update, Siemens identified the following specific workarounds and mitigations that can reduce the risk:

  • Run the software on systems within trusted networks
  • For CVE-2020-7581, ensure there is no executable at the following locations:
    — C:\Program.exe
    — C:\Program Files\Common.exe
    — C:\Program Files\Common Files\Siemens\Automation\Simatic.exe

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for Industrial Security and following the recommendations in the product manuals.

Click here for additional information on Industrial Security by Siemens.