Siemens has workarounds and mitigations to handle cross-site scripting and basic XSS vulnerabilities in its Climatix, according to a report with CISA.

Successful exploitation of these remotely exploitable vulnerabilities, discovered by Ezequiel Fernandez from Dreamlab Technologies, could allow a remote attacker to execute arbitrary code to access confidential information without authentication.

The following products of the Climatix product line suffer from the issues:

  • Climatix POL908 (BACnet/IP module); all versions
  • Climatix POL909 (AWM module); all versions

In one vulnerability, the affected product could allow an unauthenticated remote attacker to compromise the confidentiality and integrity of other users’ web sessions.

Schneider Bold

CVE-2020-7574 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 6.1.

In addition, the affected product could allow an unauthenticated remote attacker to compromise the confidentiality and integrity of other users’ web sessions.

CVE-2020-7575 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 6.1.

The product sees use mainly in the commercial facilities sector. It also sees action on a global basis.

No known public exploits specifically target this vulnerability. However, an attacker with low skill level could leverage the vulnerabilities.

Siemens identified the following specific workarounds and mitigations users can apply to reduce the risk:

  • Update Climatix POL908 and POL909 to v11.22 or later. This update does not solve the XSS issues, but disables the web interface by default, as it is no longer needed in standard use cases.
  • Climatix POL908 is designed to be operated in protected BACnet/IP networks only. Do not connect it to other networks, such as an Office LAN or the Internet. Also consider removing POL908, as the integrated BACnet/IP implementation in newer versions of Climatix 600 controllers is already sufficient for your environment.
  • The following mitigation measures apply only if the web interface is activated (e.g., via the Climatix SCOPE tool):

    • Climatix POL909: When configuring your custom web application, disable the access to the default webpages provided by POL909
    • Enforce authentication for the web interface and change the default password of the standard ADMIN user
    • Disable JavaScript within the web browser used to access the web server of Climatix POL908
    • Utilize a modern web browser with integrated XSS filtering mechanisms

    Click here for additional information on industrial security by Siemens.

    For further inquiries on security vulnerabilities in Siemens products and solutions, contact Siemens ProductCERT.

    For more information on this vulnerability, click on Siemens security advisory SSA-886514.