Siemens has updates available to handle an use of insufficiently random values vulnerability in its Linux based products, according to a report with CISA.

Successful exploitation of this remotely exploitable vulnerability, which Siemens self reported, could compromise confidentiality and integrity.

The following Siemens Linux based products suffer from the issue:
RUGGEDCOM RM1224: All versions between v5.0 and v6.4
SCALANCE M-800: All versions between v5.0 and v6.4
SCALANCE S615: All versions between v5.0 and v6.4
SCALANCE SC-600: All versions prior to v2.1.3
SCALANCE W1750D: v8.3.0.1, v8.6.0, and v8.7.0
SIMATIC Cloud Connect 7: All versions
SIMATIC MV500 Family: All versions
SIMATIC NET CP 1243-1 (incl. SIPLUS variants): Versions 3.1.39 and later
SIMATIC NET CP 1243-7 LTE EU: Versions 3.1.39 and later
SIMATIC NET CP 1243-7 LTE US: Versions 3.1.39 and later
SIMATIC NET CP 1243-7: Versions 3.1.39 and later
SIMATIC NET CP 1243-8 IRC: Versions 3.1.39 and later
SIMATIC NET CP 1542SP-1 IRC (incl. SIPLUS variants): Versions 2.0 and later
SIMATIC NET CP 1542SP-1: Versions 2.0 and later
SIMATIC NET CP 1543-1 (incl. SIPLUS variants): Versions 2.2 and later
SIMATIC NET CP 1543SP-1 (incl SIPLUS variants): Versions 2.0 and later
SIMATIC NET CP 1545-1: All versions
SINEMA Remote Connect Server: All versions prior to v3.0 SP1
TIM 1531 IRC (incl. SIPLUS NET variants): All versions

In the vulnerability, a flaw in ICMP packets in the Linux kernel may allow an attacker to quickly scan open UDP ports. This flaw allows an off-path remote attacker to effectively bypass source port UDP randomization. Software that relies on UDP source port randomization are indirectly affected as well.

CVE-2020-25705 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 7.4.

Schneider Bold

The product sees use in multiple sectors, and on a global basis.

No known public exploits specifically target this vulnerability. This vulnerability has a high attack complexity.

Siemens recommends applying updates where applicable:

Siemens identified the following workarounds and mitigations users can apply to reduce risk, so where possible, apply the following countermeasures:
— Use name servers inside corporate environments
— Restrict access of CLI and web-based management interfaces for the affected devices to a dedicated layer 2 segment/VLAN and/or controlled by firewall policies at layer 3 where possible
— Disable outgoing ICMP packets by using “service ACLs” to implement blocking rules

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends configuring the environment according to the Siemens operational guidelines for industrial security and following the recommendations in the product manuals.

For additional information, please refer to Siemens Security Advisory SSA-324955.