The remotely exploitable vulnerabilities include authentication bypass using an alternate path or channel, cleartext transmission of sensitive information, and unprotected storage of credentials.
Successful exploitation of these vulnerabilities, discovered by Irfan Ahmed and Adeen Ayub of Virginia Commonwealth University and Hyunguk Yoo of the University of New Orleans, could allow an attacker to log in as a currently or previously authenticated user or discover passwords for valid users.
Automation Direct reports these vulnerabilities affect the following CLICK PLC CPU modules: C0-1x CPUs with All firmware prior to v3.00.
In one issue, the firmware does not protect against additional software programming connections. An attacker can connect to the PLC while an existing connection is already active.
CVE-2021-32980 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 9.8.
In addition, all programming connections receive the same unlocked privileges, which can result in a privilege escalation. During the time the PLC is unlocked by an authorized user, an attacker can connect to the PLC and read the project without authorization.
CVE-2021-32984 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 9.8.
Also, after the PLC is unlocked by an authorized user, the unlocked state does not timeout. If the programming software is interrupted, the PLC remains unlocked. All subsequent programming connections are allowed without authorization. The PLC is only relocked by a power cycle, or when the programming software disconnects correctly.
CVE-2021-32986 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 9.8.
In another issue, passwords are sent as plaintext during unlocking and project transfers. An attacker who has network visibility can observe the password exchange.
CVE-2021-32982 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 7.5.
In addition, the programming protocol allows for a previously entered password and lock state to be read by an attacker. If the previously entered password was successful, the attacker can then use the password to unlock the PLC.
CVE-2021-32978 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 7.5.
The product sees use in the commercial facilities, critical manufacturing, and information technology sectors. It also sees action on a global basis.
No known public exploits specifically target these vulnerabilities. However, an attacker with low skill level can leverage the low complexity vulnerability.
Automation Direct reports these vulnerabilities are all mitigated by Version 3.00 and recommends users update software and firmware to the latest version.
Automation Direct also recommends users follow its security guidelines.