GE suggests a firmware upgrade to handle a missing authentication for critical function vulnerability in its Grid Solutions Reason RT Clocks, according to a report with CISA.
Successful exploitation of this remotely exploitable vulnerability, discovered by Ehab Hussein of IOActive, could allow access to sensitive information, execution of arbitrary code, and cause the device to become unresponsive.
The following versions of Grid Solutions Reason RT Clocks, a source of temporal synchronization signals in different formats and protocols, suffer from the issue: RT430, RT431, and RT434, all firmware versions prior to 08A05.
In the issue, the device’s vulnerability in the web application could allow multiple unauthenticated attacks that could cause serious impact. The vulnerability may allow an unauthenticated attacker to execute arbitrary commands and send a request to a specific URL that could cause the device to become unresponsive. The unauthenticated attacker may change the password of the “configuration” user account, allowing the attacker to modify the configuration of the device via the web interface using the new password. This vulnerability may also allow an unauthenticated attacker to bypass the authentication required to configure the device and reboot the system.
CVE-2020-12017 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 9.6.
The product sees use in the chemical, critical manufacturing, energy, food and agriculture, and water and wastewater systems sectors. It also sees action on a global basis.
No known public exploits specifically target this vulnerability. However, an attacker with low skill level could leverage the vulnerability.
GE recommends users of time synchronization products update their units to firmware Version 08A05 or greater to resolve these issues.
GE recommends users evaluate their current risk and implement appropriate network security mitigation measures as follows:
- Use strong network and physical security protection to prevent an attacker from reaching the local network where Reason clocks are normally installed.
- Block TCP/IP Ports 80 and 443 to block the HTTP/HTTPS access to the RT clock web interface, avoiding all vulnerabilities. The TCP/IP port blocking should end up limited to the Ethernet port interface where the RT clock is connected, using Access Control List (ACL) for instance; otherwise, other HTTP/HTTPS applications may end up affected as well.
- Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the Internet.
- Analyze security events to allow early detection of unexpected traffic/communication.
GE suggests mitigation action does not ensure complete security, but it can be considered until an upgrade on the affected time synchronization product.
Click here for more information on this vulnerability and firmware updates.