Siemens is working on a fix to handle multiple vulnerabilities in its low & high voltage power meters due to the underlying Wind River VxWorks network stack, according to a report with Siemens ProductCERT.
This stack is affected by eleven vulnerabilities known as the “Urgent/11.”
The vulnerability could allow an attacker to execute a variety of exploits for the purpose of Denial-of-Service (DoS), data extraction, and RCE, targeting availability and confidentiality of the devices and data. Siemens is working on updates for the affected products, and recommends countermeasures until fixes are available.
The following are affected products and a solution:
- Siemens Power Meters Series 9410: All versions below V2.2.1
Remediation: Update to firmware version V2.2.1 - Siemens Power Meters Series 9810: All versions
Remediation: See recommendations from workarounds and mitigations
Siemens identified the following specific workarounds and mitigations:
- Apply appropriate strategies for mitigation on the network level to ensure affected devices are as segmented
- Apply Defense-in-Depth
As a general security measure, Siemens recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens said to configure the environment according to Siemens’ operational guidelines for Industrial Security,
and to follow the recommendations in the product manuals.
Click here for additional information on Industrial Security by Siemens.
The Siemens 9410 series power and energy meters see use in energy monitoring and cost management applications. These meters end up used in local and remote monitoring of low or high-voltage electrical installations in industrial facilities, commercial buildings, utility networks or critical power environments.
The Siemens 9810 high accuracy and advanced power quality meter combines 3-phase energy and power measurement with data logging, power quality analysis, email, alarming, Modbus mastering, Transient detection, Pre-Event/Post-Event Waveform capture and extensive I/O capabilities in a modular format.
In one vulnerability, an unauthenticated attacker with network access to the device could potentially insert arbitrary code which is executed before firmware verification in the device.
CVE-2019-10938 is the case number for the issue, which has a CVSS v3.1 base score of 9.8.
Also, by sending specially crafted TCP packets with a manipulated TCP Urgent Pointer to a device, an attacker could potentially execute arbitrary code. Network access, but no authentication and no user interaction is needed to conduct this attack.
CVE-2019-12255 is the case number assigned to the issue, which has a CVSS v3.1 base score of 9.8.
In addition, by sending IPv4 packets with specially crafted IP options to a device, an attacker could potentially execute arbitrary code. Network access, but no authentication and no user interaction is needed to conduct this attack.
CVE-2019-12256 is the case number assigned to the vulnerability, which has a CVSS v3.1 base score of 9.8.
In another issue, by sending TCP packets with specially crafted TCP options to a device, an attacker could potentially trigger a Denial-of-Service (DoS) condition. Network access, but no authentication and no user interaction is needed to conduct this attack.
CVE-2019-12258 is the case number assigned to the issue, which has a CVSS v3.1 base score of 7.5.
In addition, by sending specially crafted IGMP packets to a device, an attacker could potentially trigger a Denial-of-Service (DoS) condition. Network access, but no authentication and no user interaction is needed to conduct this attack.
CVE-2019-12259 is the case number assigned to the vulnerability, which has a CVSS v3.1 base score of 7.5.
Also, by sending specially crafted TCP packets with a manipulated TCP Urgent Pointer to a device, an attacker could potentially execute arbitrary code. Network access, but no authentication and no user interaction is needed to conduct this attack.
CVE-2019-12260 is the case number assigned to the issue, which has a CVSS v3.1 base score of 9.8.
In another issue, while connecting to a remote host, specially crafted TCP packets with a manipulated TCP Urgent Pointer could potentially cause the execution of arbitrary code on the device. It is required the affected device connects to a malicious system to conduct this attack.
CVE-2019-12261 is the case number assigned to the vulnerability, which has a CVSS v3.1 base score of 8.8.
In addition, by sending unsolicited reverse ARP packets to a device, an attacker may be able to affect availability and integrity of the device. Adjacent network access, but no authentication and no user interaction is needed to conduct this attack.
CVE-2019-12262 is the case number assigned to the issue, which has a CVSS v3.1 base score of 7.1.
Also, by sending specially crafted TCP packets with a manipulated TCP Urgent Pointer to a device, an attacker could potentially trigger a race condition and potentially execute arbitrary code. Network access, but no authentication and no user interaction is needed to conduct this attack.
CVE-2019-12263 is the case number assigned to the issue, which has a CVSS v3.1 base score of 8.1.
In one last issue, by sending specially crafted IGMPv3 packets to a device, an attacker may be able to obtain a limited amount of data from the device. Network access, but no authentication and no user interaction is needed to conduct this attack.
CVE-2019-12265 is the case number assigned to the vulnerability, which has a CVSS v3.1 base score of 5.3.
For further inquiries on security vulnerabilities in Siemens products and solutions, contact Siemens ProductCERT.