The vulnerabilities include missing authentication for critical function, missing authorization, missing encryption of sensitive data, and improper restriction of rendered UI layers or frames.
Successful exploitation of this remotely exploitable vulnerability, discovered by Evgeniy Druzhinin and IIya Karpov of Rostelecom-Solar and an anonymous researcher, could allow an attacker to obtain unauthorized access to the internal product LAN, which could result in exposure of sensitive information, denial of service, and remote code execution when access to a resource from an attacker is not restricted or incorrectly restricted.
Schneider Electric reports this vulnerability affects the following firmware versions of the Easergy T300 products: Versions 2.7 and prior.
In one issue, the affected product is vulnerable to a missing authentication for critical function vulnerability, which may allow an attacker to expose information, cause a denial-of-service condition, and remotely execute arbitrary code.
CVE-2020-7561 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 10.0.
In addition, the affected product is vulnerable to a missing authorization vulnerability, which may allow an attacker to gain access to sensitive information, cause a denial-of-service condition, and remotely execute arbitrary code when access control checks are not applied consistently.
CVE-2020-28215 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 7.7.
Also, the affected product is vulnerable to a missing encryption of sensitive data vulnerability, which may allow an attacker to read network traffic over HTTP protocol.
CVE-2020-28216 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 7.6.
In another issue, the affected product is vulnerable to a missing encryption of sensitive data vulnerability, which may allow an attacker to read network traffic over IEC60870-5-104 protocol.
CVE-2020-28217 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 6.7.
In addition, the affected product is vulnerable due to an improper restriction of rendered UI layers or frames vulnerability, which may allow an attacker to trick a user into initiating an unintended action.
CVE-2020-28218 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 6.3.
The product sees action in the commercial facilities, energy, food and agriculture, government facilities, transportation systems, and water and wastewater systems sectors. It also sees action on a global basis.
No known public exploits specifically target this vulnerability. An attacker would need high skill level to exploit the issues.
Schneider Electric recommends users upgrade to v2.7.1, which is available from the Schneider Electric Customer Care Center. Alternatively, users may disable port forwarding in the product firewall.
Schneider Electric recommends the following industry cybersecurity best practices:
- Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.
- Install physical controls so no unauthorized personnel can access industrial control and safety systems, components, peripheral equipment, and networks.
- Place all controllers in locked cabinets and never leave them in “Program” mode.
- Never connect programming software to any network other than the specific network.
- Scan all methods of mobile data exchange with the isolated network (e.g., CDs, USB drives, etc.) before use in the terminals or any node connected to these networks.
- Never allow mobile devices that have connected to any other network, besides the intended network, to connect to the safety or control networks without proper sanitation.
- Minimize network exposure for all control system devices and systems and ensure they are not accessible from the Internet.
- When remote access ends up required, use secure methods, such as virtual private networks (VPNs). Recognize VPNs may have vulnerabilities and should undergo an update to the most current version available. Also, understand VPNs are only as secure as the connected devices.
For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.
Refer to Schneider Electric’s security bulletin SEVD-2020-315-06 for specific mitigation details.