Schneider Electric has versions available to handle multiple vulnerabilities in its Triconex TriStation and Triconex Tricon Communication Module, according to a report with CISA.
The remotely exploitable vulnerabilities are cleartext transmission of sensitive information, uncontrolled resource consumption, hidden functionality, and improper access control.
Successful exploitation of these vulnerabilities may allow an attacker to view clear text data on the network, cause a denial-of-service condition, or allow improper access. The vulnerabilities ended up discovered by Reid Wightman, Dragos, Inc., and Schneider Electric.
Schneider Electric discovered and remediated multiple vulnerabilities affecting the following legacy versions of its Triconex brand safety instrumented system:
- TriStation 1131, v1.0.0 to v4.9.0, v4.10.0, and 4.12.0, operating on Windows NT, Windows XP, or Windows 7.
- Tricon Communications Module (TCM) Models 4351, 4352, 4351A/B, and 4352A/B installed in Tricon v10.0 to v10.5.3 systems.
Users of current and more recent versions of the identified firmware and software are not exposed to these specific vulnerabilities.
In one issue, a vulnerability related to the “password” feature in TriStation 1131 versions 1.0 through 4.12.0 could cause certain data to be visible on the network when the feature was enabled.
CVE-2020-7483 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 5.3.
In addition, a vulnerability related to the “password” feature in TriStation 1131 versions 1.0 through 4.12.0 could allow a denial of service attack if the user is not following documented guidelines pertaining to dedicated TriStation 1131 connection and key-switch protection.
CVE-2020-7484 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 7.5.
Also, a vulnerability related to a legacy support account in TriStation 1131 versions 1.0 through 4.9.0 and 4.10.0 could allow inappropriate access to the TriStation 1131 project file.
CVE-2020-7485 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 5.5.
In another issue, a vulnerability could cause TCMs installed in Tricon system versions 10.0.0 through 10.4.x to reset when under high network load. This reset could result in a denial of service behavior with the SIS.
CVE-2020-7486 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 7.5.
In addition, a legacy debug port account in TCMs installed in Tricon system versions 10.2.0 through 10.5.3 is visible on the network and could allow inappropriate access.
CVE-2020-7491 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 10.0.
The product sees use in multiple industry sectors, and it sees action on a global basis.
No known public exploits specifically target these vulnerabilities. However, an attacker with low skill level could leverage the vulnerabilities.
Schneider Electric released TriStation v4.9.1 and v4.10.1 on May 30, 2013 and 4.13.0 on January 26, 2015 to address these issues. Tricon v10.5.0 released on August 13, 2009 and v10.5.4 on February 2, 2012 to address the issues.
Schneider Electric notified customers of updated product availability via direct-to-customer notification and fixed versions of these offers are available for download.
Schneider Electric recommends following industry cybersecurity best practices:
- Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.
- Install physical controls so no unauthorized personnel can access industrial control and safety systems, components, peripheral equipment, and networks.
- Place all controllers in locked cabinets and never leave them in the “Program” mode.
- Scan all methods of mobile data exchange with the isolated network, such as CDs, USB drives, etc., before use in the terminals or nodes connected to these networks.
- Never allow laptops that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.
- Minimize network exposure for all control system devices and systems and ensure they are not accessible from the Internet.
- When remote access is required, use secure methods such as virtual private networks.
- Recognize that VPNs may have vulnerabilities and should therefore be updated to the most current version available. Also recognize that VPNs are only as secure as the connected devices.
Schneider Electric continues to recommend users always implement the instructions in the “Security Considerations,” which include the following:
1. Ensure the cybersecurity features in Triconex solutions are always enabled
2. Always deploy safety systems on isolated networks
3. Secure all TriStation engineering workstations and never connect to any network other than the safety network
4. Configure operator stations to display an alarm whenever the Tricon key switch is in the “PROGRAM” mode
Click here to view the the Schneider Electric Security Bulletin – SESB-2020-105-01 for more details of these vulnerabilities in legacy Triconex products.