Siemens has a new version to handle multiple vulnerabilities in its SIMOTICS CONNECT 400, according to a report with CISA.

The remotely exploitable vulnerabilities are an improper null termination, out-of-bounds read, access of memory location after end of buffer, and use of insufficiently random values.

Successful exploitation of these vulnerabilities, which Siemens self-reported, could allow an attacker to poison the DNS cache or spoof DNS resolving.

The following products and versions suffer from the issues:

Schneider Bold
  • SIMOTICS CONNECT 400, All versions prior to v0.5.0.0
  • SIMOTICS CONNECT 400, v0.5.0.0 and later only affected by CVE-2021-25677

In one vulnerability, the DNS domain name label parsing functionality does not properly validate the null-terminated name in DNS-responses. The parsing of malformed responses could result in a read past the end of an allocated structure. An attacker with a privileged position in the network could leverage this vulnerability to cause a denial-of-service condition or leak the read memory.

CVE-2020-27736 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 6.5.

In addition, the DNS response parsing functionality does not properly validate various length and counts of the records. The parsing of malformed responses could result in a read past the end of an allocated structure. An attacker with a privileged position in the network could leverage this vulnerability to cause a denial-of-service condition or leak the memory past the allocated structure.

CVE-2020-27737 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 6.5.

Also, the DNS domain name record decompression functionality does not properly validate the pointer offset values. The parsing of malformed responses could result in a read access past the end of an allocated structure. An attacker with a privileged position in the network could leverage this vulnerability to cause a denial-of-service condition.

CVE-2020-27738 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 6.5.

In addition, the DNS client does not properly randomize DNS transaction IDs. This could allow an attacker to poison the DNS cache or spoof DNS resolving.

CVE-2021-25677 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 5.3.

The product sees use mainly in the energy sector, and on a global basis.

No known public exploits specifically target these vulnerabilities. However, an attacker with low skill level could leverage these low complexity vulnerabilities.

Siemens identified the following specific workarounds and mitigations users can apply to reduce risk:

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens Operational Guidelines for Industrial Security, and following the recommendations in the product manuals.

For further inquiries on security vulnerabilities in Siemens’ products and solutions, please contact Siemens ProductCERT.

Pin It on Pinterest

Share This