Siemens is in the process of working on a fix for an uncontrolled resource consumption vulnerability in its SIMATIC S7-300 CPUs and SINUMERIK Controller, according to a report with CISA.

Successful exploitation of this remotely exploitable vulnerability, discovered by WangFangLi from Beijing Winicssec Technology CO, could allow an attacker to cause a denial-of-service condition.

The vulnerability affects the following products:

  • SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants): All versions
  • SINUMERIK 840D sl: All versions

In the vulnerability, an attacker may send multiple specially crafted packets to the affected devices, which may cause a denial-of-service condition. A cold restart is required to recover the service.

Schneider Bold

CVE-2020-15783 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 5.9.

The product sees use in the chemical, critical manufacturing, and food and agriculture sectors. It also sees action on a global basis.

No known public exploits specifically target this vulnerability. High skill level is needed to exploit.

Siemens is preparing updates and recommends users protect network access to Port 102/TCP of affected devices.

As a general security measure, Siemens recommends users protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends users configure the environment according to Siemens’ operational guidelines for Industrial Security and follow the recommendations in the product manuals.

Click here for additional information on industrial security by Siemens.

For additional information, click on Siemens Security Advisory SSA-492828.