Successful exploitation of this remotely exploitable vulnerability could allow an unauthenticated attacker on the network to create and sign their own JSON web token and use it to execute an HTTP API method without the need for valid authentication/authorization. Under certain circumstances, this could be used by an attacker to impact system availability by conducting a denial-of-service attack.
Johnson Controls reports this vulnerability, discovered by Joachim Kerschbaumer, affects the following products:
- All versions of victor Web Client up to and including v5.6
- All versions of C•CURE Web Client up to and including v2.90
In the vulnerability, the software does not perform, or incorrectly performs, an authorization check when an actor attempts to access a resource or perform an action.
CVE-2020-9049 is the case number assigned to this vulnerability, which has a CVSS v3 base score of 7.1.
The product sees use mainly in the critical manufacturing sector, and on a global basis.
No known public exploits specifically target this vulnerability.
Ireland-based Johnson Controls advises users to maintain product installations at the latest release and provides several options for remediation of this issue.
- victor Web Client: upgrade to v5.6 SP1 (victor Unified Client v5.6 SP1)
For C•CURE Web Client: Upgrade to a minimum of v2.70 and install the relevant update:
- C•CURE Web v2.70: install the update Web Client_c2.70_5.2_Update02
- C•CURE Web v2.80: install the update Web Client_c2.80_v5.4.1_Update04
- C•CURE Web v2.90: install the update CCureWeb_2.90_Update01
For more detailed mitigation instructions, click on Johnson Controls Product Security Advisory JCI-PSA-2020-10.
Johnson Controls recommends taking steps to minimize risks to building automation systems.