A fire broke out on a platform in the Pacific Region November 29 near the smoke shack outside the living quarters building which started from a smoldering cigarette filter that led to a worker having to go door-to-door to get people out after the alarm failed.

An investigation into the incident by the Bureau of Safety and Environmental Enforcement (BSEE) showed a series of deficiencies and concerns regarding safety procedures on the platform.

As high winds spread the fire to an adjacent plastic storage shed, there was significant damage to the living quarters and associated areas, including steel walls, beams, and gratings. A burning cigarette filter in a cigarette receptacle appeared to be the cause of the fire, according to a BSEE report.

After realizing the General Alarm (GA) and the GAI-Tronics Public Announcement (PA) systems ended up rendered inoperable by the fire, an employee immediately began alerting crew members in the living quarters by going door to door. The Person-In-Charge then activated the fire alarm connected to a separate system.

While this case occurred on an oil platform, it could occur in any environment with interconnected alarms. A small incident like a burning cigarette filter may seem small, but the cascading effect that resulted could have led to a much larger incident.

Schneider Bold

As a result of the incident, BSEE’s investigation identified the following deficiencies and concerns related to the fire:

  • The platform’s general alarm and intercom/page system shared a circuit, which resulted in both failing due to the fire
  • Firefighting equipment in proximity to the fire location was inadequate
  • The smoking area was not effectively monitored or maintained
  • The appropriate receptacles were not used and were not properly maintained
  • A lack of understanding of the use of alarm system procedures
  • There was a large quantity of paper (i.e., combustible material) stored in a shed adjacent to the smoking area, which caused the fire to rapidly spread and engulf the storage shed.

Photo of a second cigarette butt receptacle at the site of the fire. The first receptacle ended up destroyed in the blaze.
Source: BSEE

After the investigation, BSEE recommended operators and contractors consider the following:

  • Ensure safety systems (including the PA and GA systems) are separately wired with appropriate redundancies
  • Guarantee that smoking areas are maintained and equipped with proper disposal receptacles and safety systems
  • Perform a hazard analysis to identify and mitigate potential fire hazards in the area
  • Review platform safety procedures and conduct appropriate drills
  • Review Safety Alert 354, which highlights a similar incident in 2019